P24727- Electrical Machines and Drives
Coursework-Second Attempt
Deadline For Submission: The submission deadline is as published on the Moodle drop
box associated with this submission
Submission Instructions A report containing the information required in the
assignment should be uploaded to Moodle
Instructions for completing the
assessment:
Once completed, the report should be saved as a pdf file and
uploaded to Moodle.
Examiners: Richard Walters and Branislav Vuksanovic
P24727: Electrical Machines and Drives
Lab Assignment
1. Introduction
In this project you are required to analyse and report back on an electrical machine and drive.
2. Requirements- Drives
The drive system you are to analyse is a three phase H-bridge inverter driving a ‘star’
connected load.
You should assume that the power supply voltage VS is 50V DC and that the power
devices are FET transistors. The transistors are ‘off’ when 𝑣𝐺𝑆 = 0𝑉 and is ‘on’ when
𝑣𝐺𝑆 > 5𝑉.
The circuit diagram is shown in figure 1, VQn is the input to transistor Qn. The output
voltages of each phase are VR1, VR2 and VR3, and the currents through each resistor
are IR1, IR2 and IR3.
Figure 1: Three-Phase Inverter Circuit Diagram
You should analyse two cases of the circuit during one complete cycle (360o). For each
change of input you should determine the values of VR1, VR2 and VR3, and the size
and direction of the currents IR1, IR2 and IR3. You can assume that the transistors
have zero on resistance and zero voltage drop when on. The switching of the transistors
for each case are shown in tables 1 and 2 respectively.
Having completed the analysis, you should comment of the differences between the two
cases.
Q1
2SK2553S
Q2
2SK2553S
Q3
2SK2553S
Q4
2SK2553S
Q5
2SK2553S
Q6
2SK2553S
V1
50V
R1
10Ω
R2
10Ω
R3
10Ω
VQ1
VQ2
VQ3
VQ4
VQ5
VQ6
IR2
A
IR1
A
IR3
A
VR1
V
VR2
V
VR3
V
Finally, comment on any particular issues relating to the switching of Q2, Q4 and Q6.
Angle Q1 Q2 Q3 Q4 Q5 Q6
0-120o On On
120-240o On On
240-360o On On
Table 1: Transistor Switching for Case 1
Angle Q1 Q2 Q3 Q4 Q5 Q6
0-60o On On On
60-120o On On On
120-180o On On On
180-240o On On On
240-300o On On On
300-360o On On On
Table 2: Transistor Switching for Case 1
3. Requirements- Machines
You should produce a short report on the methods of protection of distribution
transformers in transformer substations.
Your report should include a short introduction to the problem, listing and explaining
the possible types of faults and failures encountered with transformers.
In the main section of the report you should explain and discuss the methods and
technology used to protect transformers and other equipment in transformer substations
from those failures. You can choose a particular fault type and discuss it in more details
or alternatively, you can briefly describe and list the main failure and fault types and
methods as well as equipment for the protection. You can use schematic or calculations
to illustrate the problems you are discussing.
Your report should also have a short conclusion section where summary of discussion
and some conclusions about transformer protection methods and equipment will be
made.
Report should not be longer than 4 pages and should be written in IEEE paper format.
4. Reporting and Assessment
A typed report of the project should be submitted
The report should be divided into two halves, one for the drives exercise and one for
the machines exercise.
Each half should contain a short introduction to the exercise- no more than 10 linessetting
out what is expected.
Each part of the task should then be clearly presented in a separate section.
A final summary section for each half should be presented where further comments and
analysis should be presented.
Marking
Drives Case 1 10 marks
Drives Case 2 20 marks
Drives Further comments 10 marks
Drives Presentation 10 Marks
Machines - Transformer Protection Report –
Introduction
15 Marks
Machines - Transformer Protection Report -
Protection Methods and Technology
20 Marks
Machines - Transformer Protection Report -
Conclusions
15 marks
0 comments:
Post a Comment